![]() It's also possible something is wrong with the check valve and air is getting in the line from the well to the house. ![]() If the bladder is broken, you won't be able to fill it and there will be air coming out of the open faucet. ![]() ![]() If it's lower, fill it (and keep your faucet open). This should be 2-10 PSI below the "start" pressure of the pump: eg, if your pump comes on at 40psi (on at 40/off at 60 is the most common setup), the pressure tank pre-charge should be 30 to 38psi. Check the pressure in the tank using a tire pressure gauge (there is a valve on the top). To check the pre-charge, turn the pump off, and then open a faucet to let all the water out.